WITH BUNCHED COPPER : PVC INSULATED NON SHEATHED
RATED VOLTAGE 450 /
750 VOLT |
|
|
CONSTROCTION
:
2 - PVC INSULATION TYPE C |
![]() |
|
ACC. TO : IEC 227
|
|
|
Type
: H07V-K , H05V-K |
|
|
APPLICATION :
Suitable
for internal wiring of devices and for protected laying in and on lights
and for laying in conduits exposed and buried in plaster and in closed
installation ducts .They may be used for exposed conduits or embedded
conduits for signal systems . |
|
TECHNICAL INFORMATION
| NORMAL CROSS SECTION | Max. dia. of wires in conductor | INSULATION THICKNESS | SHEATH THICHNESS | APPROX. DIAMETER | APPROX. CABLE WEIGHT | Max. conductor resistance at 20°C | Pulling Tension |
| mm.2 | mm. | mm. | mm. | mm. | Kg. / Km | Ω/Km | N |
| 0.5 | 15×0.21 | 0.6 | -- | 2.2 | 9 | 39.0 | 25 |
| 0.75 | 22×0.21 | 0.6 | -- | 2.4 | 12 | 26.0 | 37.5 |
| 1.00 | 29×0.21 | 0.6 | -- | 2.5 | 14 | 19.5 | 50 |
| 1.5 | 29×0.26 | 0.7 | -- | 3.0 | 21 | 13.3 | 75 |
| 2.5 | 47×0.26 | 0.8 | -- | 3.7 | 33 | 7.98 | 125 |
| 4.0 | 53×0.31 | 0.8 | -- | 4.2 | 48 | 4.95 | 200 |
| 6 | 80×0.31 | 0.8 | -- | 4.8 | 68 | 3.30 | 300 |
| 10 | 76×0.41 | 1 | -- | 6.2 | 112 | 1.91 | 500 |
| 16 | 122×0.41 | 1 | -- | 7.4 | 171 | 1.21 | 800 |
| 25 | 190×0.41 | 1.2 | -- | 9 | 265 | 0.780 | 1250 |
| 35 | 171×0.41 | 1.2 | -- | 9.8 | 342 | 0.554 | 1750 |
| 50 | 245×0.41 | 1.4 | -- | 11.6 | 489 | 0.386 | 2500 |
| 70 | 343×0.51 | 1.6 | -- | 13.3 | 677 | 0.272 | 3500 |
| 95 | 465×0.51 | 1.6 | -- | 15.3 | 893 | 0.206 | 4750 |
| 120 | 588×0.51 | 1.6 | -- | 16.9 | 1126 | 0.161 | 6000 |
| 150 | 735×0.51 | 1.8 | -- | 18.9 | 1407 | 0.129 | 7500 |
| 185 | 906×0.51 | 2.0 | -- | 20.9 | 1712 | 0.106 | 9250 |
| 240 | 1175×0.51 | 2.2 | -- | 23.8 | 2257 | 0.0801 | 12000 |
- Insulation Resistance ≤ 0.013 MΩ