RATED VOLTAGE 0.6 / 1 KV |
|
|
CONSTRUCTION : 1 - PLAIN ANNEALED COPPER CONDUCTOR , CLASS 2 2 - XLPE INSULATION 3 - LAYING - UP 4 - FILLER OR PLASTIC TYPE 5 - PVC SHEATH TYPE ST 2
|
|
|
ACC. TO : IEC :60502 |
|
| Type : N2XY-O(J) | |
|
APPLICATION : For outdoor and indoor and installation in damp and wet locations laid direct to the ground ( When well protected ) in ducts, in trances and steel support brackets .
|
|
TECHNICAL INFORMATION
|
NOMINAL CROSS SECTION |
No. of wires & Dia. |
INSULATION THICKNESS |
Inner Covering |
SHEATH THICKNESS |
APPROX. DIAMETER |
APPROX CABLE WEIGHT |
max. conductor resistance at 20°C | min. insulation resistance 20°C | Pulling Tension |
|
mm.2 |
mm. |
mm. |
mm. |
mm. |
mm. |
Kg. / Km |
Ω/Km |
MΩ/Km |
N |
|
3×35 rm * |
7×2.52 |
0.9 |
1.0 |
1.8 |
25.8 |
1390 |
0.524 | 3.425 | 5250 |
|
3×50 rm * |
19×1.83 |
1.0 |
1.0 |
1.9 |
30 |
1660 |
0.387 | 3.148 | 7500 |
|
3×70 rm * |
19×2.17 |
1.1 |
1.2 |
2.0 |
34.6 |
2330 |
0.268 | 2.94 | 10500 |
|
3×95 rm * |
19×2.52 |
1.1 |
1.2 |
2.2 |
38.8 |
3320 |
0.193 | 2.563 | 14250 |
|
3×50 sm/25rm |
--- |
1.0/0.9 |
--- |
1.8 |
27.2 |
1850 |
0.387/0.727 | 3.148 | 8750 |
|
3×70 sm/35sm |
--- |
1.1/0.9 |
--- |
1.9 |
31.2 |
2565 |
0.268/0.524 | 2.94 | 12250 |
|
3×95 sm/50sm |
--- |
1.1/1.0 |
--- |
2.1 |
35.0 |
3460 |
0.193/0.387 | 2.563 | 16750 |
|
4×35 rm * |
7×2.52 |
0.9 |
1.0 |
1.9 |
28.5 |
1866 |
0.524 | 3.425 | 7000 |
|
4×50 rm * |
19×1.83 |
1.0 |
1.2 |
2.0 |
33.4 |
2020 |
0.387 | 3.148 | 10000 |
|
4×70 rm * |
19×2.17 |
1.1 |
1.2 |
2.2 |
38.4 |
2850 |
0.268 | 2.94 | 14000 |
|
4×95 rm * |
19×2.52 |
1.1 |
1.4 |
2.4 |
43.4 |
4000 |
0.193 | 2.563 | 19000 |
* sm shapes are available