FLEXIBLE CABLES

 

WITH BUNCHED COPPER CONDUCTOR . P.V.C INSULATED & P.V.C SHEATHED

RATED VOLTAGE 300 / 500 VOLT
 

CONSTRUCTION :

1 - PLAIN ANNEALED COPPER CONDUCTOR , CLASS 5

2 - PVC INSULATION TYPE D

3 - CORE LAID - UP TO GETHER

4 - PVC SHEATH TYPE ST 5
 

ACC. TO: BS 6500 , IEC 227

 

  Type : H05VV-F

APPLICATION :

Applications as extension and connecting cables for electrical devices ,appliances and machinery where plugs must be permanently connected to the corresponding cable .
 

TECHNICAL INFORMATION

NOMINAL  CROSS SECTION Max. dia. of wires in conductor INSULATION THICKNESS SHEATH THICKNESS APPROX. DIAMETER APPROX CABLE WEIGHT Max. conductor resistance at 20°C Min. INSULATION RESISTANCE Pulling Tension
mm.2 mm. mm. mm. mm. Kg. / Km Ω/Km MΩ / Km N
2×0.75 22×0.21 0.6 0.8 6.3 56 26.0 0.011 75
2×1 29×0.21 0.6 0.8 6.7 65 19.5 0.010 100
2×1.5 29×0.26 0.7 0.8 7.6 80 13.3 0.010 150
2×2.5 47×0.26 0.8 1 9.4 125 7.98 0.009 250
3×0.75 22×0.21 .06 0.8 6.7 66 26.0 0.011 112.5
3×1 29×0.21 0.6 0.8 7.1 77 19.5 0.010 150
3×1.5 29×0.26 0.7 0.9 8.3 110 13.3 0.010 225
3×2.5 47×0.26 0.8 1.1 10.2 170 7.98 0.009 375
4.0.75 22×0.21 0.6 0.8 7.3 81 26.0 0.011 150
4×1 29×0.21 0.6 0.9 7.9 99 19.5 0.010 200
4×1.5 29×0.26 0.7 1 9.3 140 13.3 0.010 300
4×2.5 47×0.26 0.8 1.1 11.2 212 7.98 0.009 500
5×0.75 22×0.21 0.6 0.9 8.2 102 26.0 0.011 187.5
5×1 29×0.21 0.6 0.9 8.6 120 19.5 0.010 250
5×1.5 29×0.26 0.7 1.1 10.3 175 13.3 0.010 375
5×2.5 47×0.26 0.8 1.2 12.4 264 7.98 0.009 625