ARMOURED POWER CABLES MULTI CORE XLPE INSULATED

 

WITH STANDARD & SOLID COPPER CONDUCTOR XLPE INSULATED , PVC SHEATHED

RATED VOLTAGE 0.6 / 1 KV
 

CONSTRUCTION :

1 - PLAIN ANNEALED COPPER CONDUCTOR , CLASS 2

2 - XLPE INSULATION

3 - LAYING - UP

4 - FILLER OR PLASTIC TYPE

5 - ARMOURING ( GEL, STEEL WIRE )

6 - PVC SHEATH TYPE ST 2

 

ACC. TO : IEC  60502

 

  TYPE : N2XRY , N2XFGY

APPLICATION :

 For outdoor installation in damp and wet locations, laid direct to the ground, where excessive mechanical stresses are required in sloping and movable terrains and in vertical or inclined laying, as well as in locations susceptible to sliding .

 


TECHNICAL INFORMATION
 

NOMINAL  CROSS SECTION

No. of wires & Dia.

INSULATION THICKNESS

Inner Covering

STEEL WIRE DIAMETER

SHEATH THICKNESS

APPROX. DIAMETER

APPROX CABLE WEIGHT

max. conductor resistance at 20°C min. insulation resistance 20°C Pulling Tension

mm.2

mm.

mm.

mm.

mm.

mm.

mm.

Kg. / Km

Ω/Km

MΩ/Km

N

3×35 rm *

7×2.52

0.9

1.0

40×1.6

1.9

29.2

2327

0.524 3.425 5250

3×50 rm *

19×1.83

1.0

1.0

41×2.0

2.0

34.1

2530

0.387 3.148 7500

3×70 rm *

19×2.17

1.1

1.2

48×2.0

2.2

39.0

3510

0.268 2.94 10500

3×95 rm *

19×2.52

1.1

1.2

54×2.0

2.3

43.0

4550

0.193 2.563 14250

3×120 rm *

37×2.03

1.2

1.4

49×2.5

2.5

48.7

5430

0.153 2.248 18000

3×50 sm/25rm

---

1.0/0.9

---

48×1.6

2.0

31.6

2790

0.387/0.727 3.148 8750

3×70 sm/35sm

---

1.1/0.9

---

44×2.0

2.1

36.4

4000

0.268/0.524 2.94 12250

3×95 sm/50sm

---

1.1/1.0

---

50×2.0

2.2

40.0

5000

0.193/0.387 2.563 16750

4×35 rm *

7×2.52

0.9

1.0

48×1.6

2.0

31.8

2940

0.524 3.425 7000

4×50 rm *

19×1.83

1.0

1.2

46×2.0

2.2

38.0

3100

0.387 3.148 10000

4×70 rm *

19×2.17

1.1

1.2

53×2.0

2.3

43.0

4350

0.268 2.94 14000
4×95 rm * 19×2.52

2.0

1.4

50×2.5

2.5

49.0 5550 0.193 2.563 19000


*  sm shapes are available

 

 THE A BOVE DATA IS APPROXIMATE AND SUBJECT TO MANUFACTURING TOLERANCE .