INDOOR TELEPHONE CABLES

 

 PVC INSULATED PVC SHEATHED
 

CONSTRUCTION :

1 - SOLID PLAIN ( OR TINNED ) ANNEALED COPPER CONDUCTOR

2 - PVC INSULATION TYPE Y J 1

3 - PVC SHEATH TYPE YM 1
 

ACC. TO : VDE 0815 IEC 189

 

  TYPE : JYY

APPLICATION :

Used in telephone and signal transmission, suitable for installation in dry and damp indoor enviroment. Laying under ground is not permissible. Can be installed in telephone, telefax, telex, as well as standard modems of postal services, alarm systems, communication and paging systems, access control, time & data control systems.

 


TECHNICAL INFORMATION
 

NO. OF PAIRS

CONDUCTOR DIA.

INSULATION THICKNESS

Min. SHEATH THICKNESS

Max. OVERAL DIAMETER

APPROX. CABLE WEIGHT

Max. Conductor RESISTANCE

Min. INSULATION RESISTANCE at 20°C

pair

mm.

mm.

mm.

mm.

Kg. / Km

Ω/Km MΩ/Km

2

0.5

0.2

0.4

5

23

97.8

500

4

0.5

0.2

0.6

6

36

97.8

500

6

0.5

0.2

0.6

7.4

55

97.8

500

10

0.5

0.2

0.7

8.5

75

97.8

500

20

0.5

0.2

0.8

11.5

132

97.8

500

30

0.5

0.2

0.9

13.5

196

97.8

500

40

0.5

0.2

0.9

15

250

97.8

500

50

0.5

0.2

0.9

16.5

310

97.8

500

60

0.5

0.2

0.9

18

360

97.8

500

80

0.5

0.2

1.0

20.5

475

97.8

500

100

0.5

0.2

1.0

22.5

580

97.8

500

 

CONDUCTOR SIZE 0.6 , 0.8 MM & OTHER NUMBER OF PAIRS UPON REQUEST .